Combined activation starter VELTH

Activation starter is screwed into the exterior of the generator. Triggering occurs when the threshold exceeds the temperature (180 ° C) or by an electrical impulse.

Question to purchase
Specifications

Voltage

12-24V

Minimum of inrush current

0,4 А

Type of current

Constant

Duration of electrical pulse

At least 0,5 с

Resistance of the circuit activation node

2,5-4,5 ohms (no additional resistors)

Maximum of the current at a constant monitoring of the electrical circuit transmittance must exceed

0,005 А

Maximum current during periodic monitoring of the electrical circuit transmittance must not exceed

0,05 А