Activation starter is screwed into the exterior of the generator. It is set off by an electric pulse.
The generator is a small cylinder with a metal case, on the lateral surface of which are located the outlets in a certain order. The contact cooler inside the body of the generator allows for the creation of the aerosol stream of low temperature.
Principle of operation:
By applying an electrical or thermal pulse to the activation unit, a solid aerosol charge is ignited. Combustion products passing through the contact cooler go through the outlets of the generator in the protected space.
Manufacturer's warranty:
The manufacturer guarantees the generator to abide by the technical requirements and Russian standards if the consumer adheres to the conditions specified in the instruction manual.
The warranty period for the generator - 18 months.
Utilization Period - 5 years.
Lifetime - 10 years.
Voltage |
12 V |
|
Minimum of inrush current |
1,5 А |
|
Type of current |
Constant |
|
Duration of electrical pulse |
At least 2,0 с |
|
Resistance of the circuit activation node |
7,5-8,0 ohms (no additional resistors) |
|
Maximum of the current at a constant monitoring of the electrical circuit transmittance must exceed |
0,005 А |
|
Maximum current during periodic monitoring of the electrical circuit transmittance must not exceed |
0,05 А
|