Fire Extinguishing Aerosol Generator AGS-2/4

Designed to generate a mixture of gas and aerosol, a necessary volumetric concentration which stops the flame from burning.

AGS-2/4 is resistant to vibration, and is therefore recommended for the protection of vehicles. It is also used in areas of average volume. AGS-2/4 has a number of modifications in types of attachment and the direction of aerosol spray.

Question to purchase
Description

The AGS 2/4 is cylinder-shaped with a metal case, and has a nozzle cap on the exterior. Due to the contact cooler inside the body, it has a low temperature aerosol spray.

Principle of operation:

By applying an electrical pulse to the activation unit that is installed inside the generator, the aerosol charge is ignited. Combustion products passing through the cooling unit, exit through the nozzle on the cover of the generator and enter the protected area.

Manufacturer's warranty:

The manufacturer guarantees the generator agrees with the Russian National Standard technical requirements if the consumer abides by the instructions specified in the instruction manual.

The warranty period for the generator - 18 months.

Utilization period - 5 years.

Lifetime - 10 years

Activation units


* Type of the activation unit selected by the customer and installed in the generator
Specifications

Maximum protected volume in sealed room
(d * <0,001 m-1)

21 m3

Curb weight of the generator

5,1 kg

Weight of the aerosol charge

1,7 kg

Working time

40 minutes

Dimensions

Diameter

167 mm

Height

180 mm

Activation unit

UST-7.5

Resistance of the activation unit

7,8±0,8 ohm

Minimum start-up current

1.5А

Starting voltage

12

The duration of the trigger pulse

not less than 2.0 sec

The inertia of the generator

< 2,0 sec

Operating Conditions

Operating Temperature Range

± 50 °С

relative humidity at 25 ° C.

98 %

mechanical influences (in the frequency range up to 100 Hz)

1g

Classes of fire-fighting

a-class.gif b-class.gif

Modifications
AGS-2 / 4-1-1-1
Aerosol exits through the generator axis. Mounted on stand.
AGS-2 / 4-2-1-1
Aerosol exits through the generator axis. Mounted on flange.
АГС-2 / 4-1-2-1
Aerosol exits through the generator axis. Mounted on stand.
AGS-2 / 4-2-2-1
Aerosol exits through 360* perimeter. Mounted on flange.
AGS-2 / 4-1-1-2
Aerosol exits through the generator axis. Mounted on stand.
AGS-2 / 4-2-1-2
Aerosol exits through the generator axis. Mounted on flange.
АГС-2 / 4-1-2-2
Aerosol exits through the generator axis. Mounted on stand.
AGS-2 / 4-2-2-2
Aerosol exits through 360* perimeter. Mounted on flange.
Articles Fire extinguishing systems in archives, статьи Гранит-Саламандра
Fire extinguishing systems in archives
In archives, libraries, book-depositories the huge mass of papers of information which represents sometimes great cultural, historical, practical value are concentrated.
Fire safety service stations, статьи Гранит-Саламандра
Fire safety service stations
Petrol stations can be attributed to the objects with a high risk of fire due to the large amounts of combustible materials and explosive vapor concentrations. In this regard, at the gas station are increased requirements for fire safety, in particular, to equip the automatic fire extinguishing agents.
Firefighting in the boiler room, статьи Гранит-Саламандра
Firefighting in the boiler room
Boiler room - technical room is designed to heat the coolant and transmission in water and heating systems. In view of the complex and explosive equipment and the use of different fuels, boilers necessarily equipped with a fire alarm system and effective fire-fighting installations.

Question to purchase AGS-2/4

We guarantee that the personal data you provide us will be used solely for the purposes of processing your requests. We work in accordance with the Federal Law of July 27, 2006 N 152-FZ «ABOUT PERSONAL DATA».

Mandatory field.

With contact cooling