Products
Main : Products :: Aerosol fire extinguishers ::: With contact cooling :::: AGS-6/2

Aerosol Fire-Extinguishing Generator AGS-6/2

Designed for generating gas-aerosol mixture at the concentrations required to stop a fire.

It is recommended to form fire-extinguishing systems for premises of average volumes.

Question to purchase
Description

The generator is a small cylinder with a metal case, on the lateral surface of which are located the outlets in a certain order. The contact cooler inside the body of the generator allows for the creation of the aerosol stream of low temperature.

Principle of operation:

By applying an electrical or thermal pulse to the activation unit, a solid aerosol charge is ignited. Combustion products passing through the contact cooler go through the outlets of the generator in the protected space.

Manufacturer's warranty:

The manufacturer guarantees the generator to abide by the technical requirements and Russian standards if the consumer adheres to the conditions specified in the instruction manual.

The warranty period for the generator - 18 months.

Utilization Period - 5 years.

Lifetime - 10 years.

Specifications

Maximum protected volume conditionally sealed room 
(d * <0,001 m-1)

52 m3

Curb weight of the generator

14.0 kg

Weight aerosol charge

3.58 kg

Working time

40

Dimensions

Width

294 mm

Height

420 mm

Activation unit

BP-7.5-7.5 VRTH

VEE, VELTH

Resistance of the activation unit

7.5± 0.8 ohm

2.5 – 4 ohm

Minimum start-up current

0.4 А

Starting voltage

8 – 30

1.5 – 24

The duration of the trigger pulse

not less than 1.5 sec

not less than 0.1 sec

The inertia of the generator start

<1.5 sec

Operating Conditions

Operating Temperature Range

± 50 °С.

relative humidity at 25 ° C.

98 %

mechanical influences (in the frequency range up to 100 Hz)

1g

Classes of fire-fighting



Articles Fire extinguishing systems in archives, статьи Гранит-Саламандра
Fire extinguishing systems in archives
In archives, libraries, book-depositories the huge mass of papers of information which represents sometimes great cultural, historical, practical value are concentrated.
Fire safety service stations, статьи Гранит-Саламандра
Fire safety service stations
Petrol stations can be attributed to the objects with a high risk of fire due to the large amounts of combustible materials and explosive vapor concentrations. In this regard, at the gas station are increased requirements for fire safety, in particular, to equip the automatic fire extinguishing agents.
Fire safety in transport, статьи Гранит-Саламандра
Fire safety in transport
People are always wary of fire - a powerful element that is difficult to control in all conditions, including in public transport.
Advantages of the aerosol fire extinguishing generator, статьи Гранит-Саламандра
Advantages of the aerosol fire extinguishing generator
In order to successfully put out fires and save lives, health and property, aerosol fire extinguishing generators are now widely used. Their principle of operation is significantly different from the principle of the traditional means of extinguishing a fire, which leads to a number of advantages of such equipment.
Firefighting in the boiler room, статьи Гранит-Саламандра
Firefighting in the boiler room
Boiler room - technical room is designed to heat the coolant and transmission in water and heating systems. In view of the complex and explosive equipment and the use of different fuels, boilers necessarily equipped with a fire alarm system and effective fire-fighting installations.
Equipment for organization of aerosol fire-extinguishing systems, статьи Гранит-Саламандра
Equipment for organization of aerosol fire-extinguishing systems
Aerosol fire - the most effective way of ensuring fire safety in confined spaces. The aerosol fire extinguishing generators act as fire-fighting equipment.
Fire safety of garages, статьи Гранит-Саламандра
Fire safety of garages
Garage enterprises and private garages are classified as inflammable objects, which is largely due to the presence of combustible substances - fuel, gas mixtures, oils, paint formulations. To enhance the level of fire safety in the garage is necessary to observe appropriate safety precautions and the use of modern fire-fighting system.

Question to purchase AGS-6/2

We guarantee that the personal data you provide us will be used solely for the purposes of processing your requests. We work in accordance with the Federal Law of July 27, 2006 N 152-FZ «ABOUT PERSONAL DATA».

Mandatory field.

With contact cooling